Title 24, CALGreen and the Civil Code 1101 Fixture Rule for Remodels

Every permitted kitchen or bathroom remodel in Pasadena, CA brings in a set of California rules beyond the room itself: Civil Code 1101.4 for water-saving fixtures across the house, CALGreen flow rates and material limits, and Title 24 energy rules for lighting, ventilation and insulation. This guide lists them as the City of Pasadena's remodel handouts state them. Last reviewed October 2026.

  • Civil Code 1101.4
  • CALGreen flow rates
  • Title 24 lighting
  • Fans and insulation
Get a Free Quote

Civil Code 1101.4: the whole-house fixture rule

California Civil Code 1101.4 is the rule most remodelers' clients haven't heard of. When a building permit is issued for remodeling a house built before January 1, 1994, every non-compliant plumbing fixture in the house is upgraded to a water-conserving one, including fixtures outside the scope of work. A bathroom remodel can mean a new toilet in the other bathroom too.

Non-compliant fixtures and the CALGreen replacements
FixtureNon-compliant aboveReplacement maximum (CALGreen 4.303)
Toilet (water closet)1.6 gallons per flush1.28 gallons per flush
Urinal1.0 gallon per flush0.125 gpf wall-mount; 0.5 others
Showerhead2.5 gallons per minute1.8 gpm at 80 psi
Bathroom faucet2.2 gpm1.2 gpm at 60 psi
Kitchen faucet2.2 gpm1.8 gpm at 60 psi

Swipe the table sideways to see every column →

As listed in the City of Pasadena's Residential Bathroom and Kitchen Remodel handouts (2020).

Walk-in shower with marble-look wall tile, a recessed niche and a glass panel, next to the toilet
Walk-in shower with marble-look wall tile, a recessed niche and a glass panel, next to the toilet.

Title 24 lighting in kitchens and baths

Kitchens

  • Every installed luminaire high efficacy, including permanently installed lights in and under cabinets
  • Cabinet lighting switched separately from the room's other lighting
  • Recessed fixtures IC-rated and certified airtight
  • In condos with a rated floor/ceiling between units, recessed fixtures protected to match the rating

Bathrooms

  • Every installed luminaire high efficacy, with at least one controlled by a vacancy sensor
  • No switch inside a tub or shower space
  • No pendant within 3 feet horizontally and 8 feet vertically of a tub rim or shower threshold
  • Fixtures over the tub or shower enclosed, gasketed, rated for damp or wet locations and GFCI protected
White shaker cabinets with under-cabinet lighting, a subway tile backsplash and a range under a hood
White shaker cabinets with under-cabinet lighting, a subway tile backsplash and a range under a hood.

Ventilation: bathroom fans and kitchen hoods

Exhaust requirements
RoomRequirement
Bathroom with tub, shower or spaVented outdoors; 50 cfm intermittent or 20 cfm continuous; 3 sone max (1 continuous); humidistat 50 to 80% RH
Bathroom with only toilet and sinkNo fan needed with an operable window of at least 3 sq ft
Bath fan switchingSeparate from the lights, or lights that turn off while the fan keeps running
Bath duct outletOutside the building, backdraft damper, 3 ft from property line and openings, 10 ft from air inlets
Kitchen hoodVented outdoors (no recirculation); 100 cfm intermittent or 5 air changes per hour continuous; 3 sone max
Kitchen ductSmooth metal, no aluminum flex, backdraft damper
Hood verificationHERS rater, unless over 400 cfm at minimum speed (2019 code edition)

Swipe the table sideways to see every column →

City of Pasadena Residential Bathroom Remodel and Residential Kitchen Remodel handouts, citing the Energy Code, ASHRAE 62.2, CALGreen 4.506.1 and the Mechanical Code.

Insulation and air sealing

A remodel that opens exterior walls or a ceiling has to insulate what it exposes: R-13 minimum in 2x4 walls, R-19 in 2x6 or deeper, and R-19 in ceilings, with accessible joints and penetrations in the building envelope caulked or sealed. In older Pasadena houses with uninsulated plaster walls, opening the kitchen's exterior wall is often the first time it gets insulation.

Worker caulking a window frame in a kitchen with the counters covered in plastic
Worker caulking a window frame in a kitchen with the counters covered in plastic.

CALGreen material rules

  • Adhesives, sealants, caulks, paints and coatings within CALGreen's VOC limits
  • Aerosol paints within the reactivity (MIR) limits
  • At least 80% of installed resilient flooring certified to CALGreen's emissions criteria
  • Hardwood plywood, particleboard and MDF within the formaldehyde limits, which matters for cabinets
  • No new framing closed in above 19% moisture content

Which edition applies

Pasadena's handouts were written to the 2019 codes. The California Energy Commission states that buildings whose permit applications are filed on or after January 1, 2026 must comply with the 2025 Energy Code, so some details (hood verification thresholds, for example) may have moved. The City's Building & Safety Division has the current version.

How these rules show up in a project: the bathroom remodel and kitchen remodel pages, the permit guide, and for pre-1994 houses with original fixtures, the Craftsman and historic remodel page.

Request a Free Quote

Four fields. Free, and nothing is committed.

California Remodel Code Rules: Questions

What are the CALGreen plumbing fixture flow rates?

As listed in Pasadena's remodel handouts: toilets 1.28 gallons per flush, showerheads 1.8 gallons per minute at 80 psi, bathroom faucets 1.2 gpm at 60 psi, kitchen faucets 1.8 gpm at 60 psi, wall-mount urinals 0.125 gallons per flush.

Does Civil Code 1101.4 apply to my house?

If it was built before January 1, 1994 and you get a building permit for remodeling, yes: non-compliant fixtures throughout the house get upgraded, not just in the remodeled room. Houses built on or after that date are exempt.

What lighting does Title 24 require in a kitchen?

Under Pasadena's handout, every installed luminaire must be high efficacy, including lights in and under cabinets, which are switched separately from other lighting. Recessed fixtures must be IC-rated and certified airtight.

Does a bathroom fan need a humidity control?

Yes, in a bathroom with a tub, shower or spa. The handout calls for a fan vented outdoors at 50 cfm (20 cfm if it runs continuously), no louder than 3 sone (1 sone continuous), controlled by a humidistat adjustable between 50 and 80 percent relative humidity.

Does my range hood need to be tested?

Pasadena's kitchen handout (2019 code) says range hoods are verified by a HERS rater unless they exhaust more than 400 cfm at minimum speed. Permits filed since January 1, 2026 fall under the 2025 Energy Code, so confirm the current rule with the City.

Do I have to insulate during a remodel?

Where the remodel exposes them: exterior walls get at least R-13 in 2x4 framing or R-19 in 2x6, and ceilings R-19, and accessible gaps in the building envelope are sealed, per the City's handouts.